[
Home |
User's Guide Archive |
PollCat Products |
NetReach Products |
Contact WTI ]
9. Application Examples
9.1. Monitoring Signal Drop and/or Power Loss
In this application, the PLS-345 will monitor the DTR signal from a data
device. If the signal drops or the data device loses power for more than
one minute, the unit will automatically switch circuits 2 and 3 to the "B"
line.
Figure 9.1: Monitoring Signal Drop
- Connect Line from Data Device: Connect a line from the Data
Device to the Monitor Input Connector as shown in Figure 9.1.
- Set Monitor Selector Switch: Locate the Monitor Selector
Switch on the PLS back panel. Slide the switch to the "RS232"
position.
Figure 9.2: AUX Port Connection
- Configure Monitor Mode: Access the PLS command
mode as described in Section 5.2. At the PLS> command prompt, type
/M [Enter] to
display the Monitor Mode Parameters Menu. Note that the Monitor Mode
Parameters Menu is not available in User Mode. Set Monitor Mode Parameters
as follows:
- Item 1 - Monitor Mode: On.
Note: Do not enable the
Monitor Mode until you have finished defining the other Monitor Mode
parameters.
- Item 2 - Switch if Level: 0 - Low.
- Item 3 - Switch to Position: B.
- Item 4 - Delay Period: 1 Minute.
- Item 5 - Return: Off (Note that if you wanted the A/B
circuits to return to their original positions if the monitored line goes
high again, then this item would be enabled.)
- Item 6 - Circuits to Switch: Enable the Monitor Mode at
circuits 2 and 3.
- Set Circuit Parameters: From the PLS command
prompt, type /P 2 [Enter] to display the Circuit 2 Parameters Menu. Use
item 4 (Default Position) in the Circuit Parameters Menu to set the default
state for Circuit 2 to "A". Repeat this procedure for Circuit 3 (use the /P
3 command to access the Circuit 3 Parameters Menu.)
- Operation: When the DTR signal is present (high), Circuits
2 and 3 will remain in the default (A) position. If the DTR drops for more
than one minute, PLS A/B Circuits 2 and 3 will be switched to the "B"
position.
9.2. Monitoring a Contact
In this application, the PLS will monitor a switch or contact. When the
contact closes (signal goes low) for more than one minute, the PLS will
automatically switch module 1 to the "B" position. Later, if the contact
returns to the open position, the PLS will return circuit 1 to the "A"
position.
Figure 9.3: Monitoring a Switch or Relay
Note: This example could
also be used to monitor a contact or switch that is normally closed. To
automatically switch A/B circuits when a contact is opened, use item 3
(Switch if Level) in the Monitor Mode Parameters Menu (Section 5.7.2) to
select the "1 - High" option.
- Connect Line from Data Device: Connect a line from the
contact to the Monitor Input Connector as shown in Figure 9.3.
- Set Monitor Selector Switch: Locate the Monitor Selector
Switch on the PLS back panel. Slide the switch to the "CONTACT"
position.
Figure 9.4: AUX Port Connection
- Configure Monitor Mode: Access the PLS command
mode as described in Section 5.2. At the PLS> command prompt, type
/M [Enter] to
display the Monitor Mode Parameters Menu. Note that the Monitor Mode
Parameters Menu is not available in User Mode. Set Monitor Mode Parameters
as follows:
- Item 1 - Monitor Mode: On.
Note: Do not enable the
Monitor Mode until you have finished defining the other Monitor Mode
parameters.
- Item 2 - Switch if Level: 0 - Low.
- Item 3 - Switch to Position: B.
- Item 4 - Delay Period: 1 Minute.
- Item 5 - Return: On (This will instruct the PLS to switch
Circuit 1 back to the "A" position if the signal goes high again, and
remains high for one minute.)
- Item 6 - Circuits to Switch: Enable the Monitor Mode at
circuit 1.
- Set Circuit Parameters: From the PLS command
prompt, type /P 1 [Enter] to display the Circuit 1 Parameters Menu. Use
item 4 (Default Position) in the Circuit Parameters Menu to set the default
state for Circuit 2 to "A".
- Operation: When the switch is open, the input level will
remain high, and Circuit 1 will remain in the "A" position. If the switch
closes for more than one minute, the input level will drop, and Circuit 1
will be automatically switched to the "B" position. If the switch returns
to the open position, and remains open for one minute, then Circuit 1 will
return to the "A" position.